American Nuclear Society
Home

Home / Publications / Journals / Nuclear Technology / Volume 23 / Number 2

Removal of Iodine by Sprays in the PSICO 10 Model Containment Vessel

S. Barsali, R. Bovalini, F. Fineschi, B. Guerrini, S. Lanza, M. Mazzini, R. Mirandola

Nuclear Technology / Volume 23 / Number 2 / August 1974 / Pages 146-156

Reactor / Nuclear Safeguards (Presented at November 1973 Meeting) / dx.doi.org/10.13182/NT74-A31448

Twelve experimental runs on molecular iodine removal by sprays were carried out in the 95m3 PSICO 10 model containment vessel (MCV). Both service water and a water solution containing 1% sodium thiosulphate were sprayed through two different nozzles; the elemental iodine removal half-times obtained by spraying service water do not differ greatly from those found by spraying thiosulphate solution. The sprayed solution was, in some cases, recirculated for a period ranging from 1 to 11 h without any release of iodine to the atmosphere. Some runs were performed with fractions of the MCV volume not sprayed. The elemental iodine removal half-times in the sprayed and unsprayed regions do not essentially differ.