Nuclear Science and Engineering / Volume 72 / Number 1 / October 1979 / Pages 84-96
Technical Paper / dx.doi.org/10.13182/NSE79-A19311
Articles are hosted by Taylor and Francis Online.
A new modeling technique is introduced for on-line sensor time constant identification, both for the resistance temperature detector (RTD) and for the pressure sensor using power plant operational data. The sensor's time constant is estimated from a real characteristic root of the fitted autoregressive moving average model The RTD's time constant values were identified to be 8.4 s, with a standard deviation of 1.2 s. The pressure sensor time constant was identified to be 28.6 ms, with a standard deviation of 3.5 ms.