American Nuclear Society
Home

Home / Publications / Journals / Fusion Science and Technology / Volume 54 / Number 1

Operational Results of the Safety Systems of the Tritium Process Laboratory of the Japan Atomic Energy Agency

Toshihiko Yamanishi et al.

Fusion Science and Technology / Volume 54 / Number 1 / July 2008 / Pages 315-318

Technical Paper / Environment and Safety / dx.doi.org/10.13182/FST08-A1821

The building and safety systems of the TPL (Tritium Process Laboratory) were constructed in 1984 and 1985. The safety systems in the TPL have operated with tritium since March 1988. The amount of tritium held in the TPL was 13 PBq in March 2007. The average tritium concentration in a stream from a stack of the TPL to the environment was 6.0 x 10-3 Bq/cm3 and is 1/100 smaller than that of the regulatory value for the concentration of HTO in the air in Japan. Safe operation with tritium has been demonstrated. A set of failure data for several main components of the TPL was also obtained as valuable data for a fusion tritium facility.